Page 119 - PRESS-FIT SYSTEMS FOR DIVERSE APPLICATIONS
P. 119
XPRESS STAINLESS STEEL TUBE
(SS600/SS620) 1.4401 (AISI 316) TECHNICAL CHARACTERISTICS
The XPress stainless steel tube has Stainless steel tube X5CrNiMo 17 12 2 Material no. 1.4401
been tested and approved for potable Material according to DIN-EN 10088-2
water installations by many international
certification institutes including WRAS, DVGW, SVGW, ETA, ÖVGW, BYGGFORSK, STF, PZH, SITAC,
LPCB, to DVGW/DIN and DVGW- Approvals CSTBat, WRAS, VdS, FM, FG, CNBOP, SBSC, SETSCO, LPCB,
DNV, GL, LR, UL, cUL
Worksheet GW541.
As part of the DVGW/BSI (formerly Tolerances According to EN 10312 Table 2
GL,British Gas) approvals process, XPress
Stainless Steel Gas fittings have passed
the High Temperature Leakage Rate Test Finishing Annealed under a protective atmosphere W2R
at 650°C for 30 minutes at PN5/GT1.
The maximum working pressure inside
buildings is 1bar and outside buildings is Surface finish Matt silver coloured
5bar (maximum pressure test 7.5bar)
SudoXPress Stainless DN[ ]/[size x wall thickness]mm, Stainless steel/
Edelstahl-Sanitary/Sanitar –GAS, 1.4001/AISI316, EN10312, DVGW GW541
Reg. Nr. DW-7301BM5610, SVGW, ÖVGW W1.397 WRAS, ETA, BYGGFORSK,
APPLICATIONS Marking STF, PZH, SITAC 0168/04, CSTBat 116-1482, LPCB, VdS G4080007 [working
pressureVdS] bar, <FM> [workingpressure FM] psi, C(UL)US Listed 4NB1
Installations always have to comply [working pressure UL] psi, DNV, GL, NDE, [batch number or production date],
with local regulations [supplier code] [max.every 60cm the model designation repeated]
Suitable for a wide range of 15mm to 28mm - 3.5 x external diameter of the tube.
applications including (H.W.G.S) Smallest bending radius 35mm & above - bending is not recommended
Heating, Water, Gas & Stainless
Sprinkler System
Supply mode Tubes, length of 6m +0/-50mm, with protective caps (Green)
All potable water installations in
accordance with international drinking
water institutes, for example, WRAS Heat expansion coefficient 0.0160mm/m with∆T=1K
the German Potable Water Decree
(TrinkwV) and EU council
directive98/83/EC, DIN50930 Part 6 Max. operating pressure 16bar
and in compliance with DIN 1988
Water supply and rain water
installations
Potable water for industrial Conditioned installations for burnable
applications gases: natural gases and liquid gases
Wet and dry fire mains in accordance according to DVGW Worksheet
with DIN 1988 Part 6, VdS, FG, G260 I/II. Installations of gas and
CNBOP, SBSC, FM, LPCB and UL/CUL liquid gas conducting tube
installations according to DVGW –
Conditioned water such as decalcified/ Worksheet G600, DVGW- TRGI 86/89
softened water, partly and completely and TRF 1996.
desalinated water, distilled water,
water with glycol.* *Further additives for antifreeze must be compatible
with EPDM O Rings. Approval must be sought from
Compressed air (see page 133) Pegler Yorkshire prior to installation.
119