Page 119 - PRESS-FIT SYSTEMS FOR DIVERSE APPLICATIONS
P. 119

XPRESS STAINLESS STEEL TUBE
            (SS600/SS620) 1.4401 (AISI 316)                           TECHNICAL CHARACTERISTICS
            The XPress stainless steel tube has                              Stainless steel tube X5CrNiMo 17 12 2 Material no. 1.4401
            been tested and approved for potable         Material                   according to DIN-EN 10088-2
            water installations by many international
            certification institutes including WRAS,                        DVGW, SVGW, ETA, ÖVGW, BYGGFORSK, STF, PZH, SITAC,
            LPCB, to DVGW/DIN and DVGW-                  Approvals          CSTBat, WRAS, VdS, FM, FG, CNBOP, SBSC, SETSCO, LPCB,
                                                                                      DNV, GL, LR, UL, cUL
            Worksheet GW541.
            As part of the DVGW/BSI (formerly            Tolerances                 According to EN 10312 Table 2
            GL,British Gas) approvals process, XPress
            Stainless Steel Gas fittings have passed
            the High Temperature Leakage Rate Test       Finishing               Annealed under a protective atmosphere W2R
            at 650°C for 30 minutes at PN5/GT1.
            The maximum working pressure inside
            buildings is 1bar and outside buildings is   Surface finish                Matt silver coloured
            5bar (maximum pressure test 7.5bar)
                                                                           SudoXPress Stainless DN[ ]/[size x wall thickness]mm, Stainless steel/
                                                                         Edelstahl-Sanitary/Sanitar –GAS, 1.4001/AISI316, EN10312, DVGW GW541
                                                                        Reg. Nr. DW-7301BM5610, SVGW, ÖVGW W1.397 WRAS, ETA, BYGGFORSK,
            APPLICATIONS                                 Marking         STF, PZH, SITAC 0168/04, CSTBat 116-1482, LPCB, VdS G4080007 [working
                                                                          pressureVdS] bar, <FM> [workingpressure FM] psi, C(UL)US Listed 4NB1
               Installations always have to comply                      [working pressure UL] psi, DNV, GL, NDE, [batch number or production date],
               with local regulations                                      [supplier code] [max.every 60cm the model designation repeated]
               Suitable for a wide range of                                   15mm to 28mm - 3.5 x external diameter of the tube.
               applications including (H.W.G.S)       Smallest bending radius  35mm & above - bending is not recommended
               Heating, Water, Gas & Stainless
               Sprinkler System
                                                        Supply mode         Tubes, length of 6m +0/-50mm, with protective caps (Green)
                All potable water installations in
               accordance with international drinking
               water institutes, for example, WRAS    Heat expansion coefficient     0.0160mm/m with∆T=1K
               the German Potable Water Decree
               (TrinkwV) and EU council
               directive98/83/EC, DIN50930 Part 6    Max. operating pressure              16bar
               and in compliance with DIN 1988
               Water supply and rain water
               installations
               Potable water for industrial       Conditioned installations for burnable
               applications                       gases: natural gases and liquid gases
                Wet and dry fire mains in accordance       according to DVGW Worksheet
               with DIN 1988 Part 6, VdS, FG,       G260 I/II. Installations of gas and
               CNBOP, SBSC, FM, LPCB and UL/CUL     liquid gas conducting tube
                                                  installations according to DVGW –
               Conditioned water such as decalcified/      Worksheet G600, DVGW- TRGI 86/89
               softened water, partly and completely       and TRF 1996.
               desalinated water, distilled water,
               water with glycol.*             *Further additives for antifreeze must be compatible
                                               with EPDM O Rings. Approval must be sought from
               Compressed air (see page 133)   Pegler Yorkshire prior to installation.










                                                                                                                    119
   114   115   116   117   118   119   120   121   122   123   124