Page 124 - PRESS-FIT SYSTEMS FOR DIVERSE APPLICATIONS
P. 124

3.0 TECHNICAL DATA
            XPRESS TUBE MANUFACTURING

            SPECIFICATIONS





                                                   MANUFACTURING SPECIFICATIONS

                    Product           Specification       Type of tubing  Welding deterioration reduction  Weld slag removal


                                                                            100% EDDY CURRENT
                                   EN 10312-DVGW worksheet
              SS600 (AISI 316) Stainless steel           TIG or laser welded  tested according to  Outside
                                    GW541(2004) Table 2
                                                                            SEP 1914/EN 10246-2
                                                                            100% EDDY CURRENT
              SS610 (AISI 316) Stainless steel  EN 10312 Table 1  TIG welded  tested according to   N/A
                                                                              BS EN 10246-2


                                                                            100% EDDY CURRENT
                                   EN 10312-DVGW worksheet
              SS620 (AISI 316) Stainless steel           TIG or laser welded  tested according to  Outside
                                    GW541(2004) Table 2
                                                                            SEP 1914/EN 10246-2
                                                                            100% EDDY CURRENT
                                   EN 10312-DVGW worksheet
              SS630 (AISI 444) Stainless steel            Laser welded       tested according to   Outside
                                    GW541(2004) Table 2
                                                                            SEP 1914/EN 10246-2
                                                                            100% EDDY CURRENT
              SS640 (AISI 439) Stainless steel  EN 10296-2  Laser welded     tested according to   Outside
                                                                            SEP 1914/EN 10246-2


                                                                            100% EDDY CURRENT  Outside flat, inside raise
                 SC640 Carbon steel    EN 10305-3          HF welded         tested according to  max.0.5mm
                                                                            SEP 1914/EN 10246-2


                                                                            100% EDDY CURRENT  Outside weld flat insight
                 SC645 Carbon steel    EN 10305-3          HF welded         tested according to  raising max.0.5mm for
                                                                               SEP-1925       dimensions >54mm 0.8mm

                                                                           100% EDDY CURRENT or
                                       EN 10305-3
                SC660 Stainless steel                     Laser welded       tested according to   Outside
                                    (previously DIN 2394)
                                                                            SEP 1914/EN 10246-2

            TRANSPORT AND STORAGE
            We recommend that tube is not left exposed to the elements, and   wooden blocks. Bundles should not be stacked higher than the
            that end caps remain in place during storage.      recommended maximum height in order to prevent tubes from
                                                               becoming oval (the maximum height should not exceed 6 bundles,
            During transport and storage of XPress Sprinkler tubes and press
            fittings it is important to avoid damage and soiling. The best   when stacking stack in 2x2/3x3, etc.). Please ensure that carbon and
            storage temperature for fittings and tubes is between 10°C and   stainless tubes are stored seperately.
            25°C and they should be stored in a dry area (maximum humidity
            65%). The storage of tubes should be horizontal, separated by








  124