Page 106 - PRESS-FIT SYSTEMS FOR DIVERSE APPLICATIONS
P. 106

3.0 TECHNICAL DATA
            VALVES FOR THE XPRESS SYSTEM






            The XPress range is supported by a
            comprehensive selection of adapted press-fit
            valves from Pegler Yorkshire’s Ballorex and
            Pegler valve portfolios.  The valves are
            available with standard XPress press-fit by
            XPress press-fit ends (PS) or XPress press-fit
            by XPress press union ends (PSU).                                                                      A
            XPress press union ends provide an
            ideal break points that enables system
            maintenance and for equipment to be
            disconnected and reconnected for servicing.


             BALLOREX
             Dynamic Valve (PICV)     A
             For automatic balancing of
             sections of pipe work and                                                                             B
             equipment in HVAC applications.
             Dynamic PICV (Pressure Independent                                       F       F
             Control Valve) with direct flow
             measuring. Available in sizes 15mm
             to 18mm (PS)  and 35mm to 54mm
             (PSU).
                                                                                      F


                                                                                                                   B
                                                                                      F       F
             BALLOREX
             Fixed Orifice Commissioning   B
             Valve (FODRV)
             For the isolation and balancing of
             sections of pipe work and equipment
             in HVAC applications. Valves can be
             double regulated and closed to a
             pre-selected value, set when
             commissioned. Available in sizes 15mm
             to 54mm (PS)  and 15mm to 54mm (PSU)
             on both outlet or inlet.
             Alternatively Ballorex Venturi
             Commissioning valve (FODRV) are also
             available for maximum accuracy of
             +/-3%.

             BALLOREX                                           PEGLER
             Circulation Valve        C                         Pressure Reducing Valve   D
             Enables the automatic thermal                      Enables potentially damaging water
             balancing and high temperature                     pressures to be reduced. Adjustable
             disinfection of hot water circulating              0.5 to 6.0 bar. Available in sizes 15mm
             systems, denying bacteria the                      to 54mm (PS)  and 15mm to 28mm
             optimum conditions for growth.                     (PSU).
             Available in sizes 15mm to 28mm (PS
             and PSU).









  106
   101   102   103   104   105   106   107   108   109   110   111