3. DEBURR AND CHECK THE TUBE ENDS:                         PIPEWORK CLEARANCE
            Both the internal and external tube ends should be deburred then wiped   When designing an XPress System, please take care
            clean of all swarf and debris to avoid damage to the O ring upon tube   to ensure all joints can be accessed easily. Observe
            insertion.  Also check that the tube end is clean and free from damage such as   minimum gaps and insertion distances to ensure
            scores, tape, labels or adhesive residue.                  sufficient access for the pressing tool, where applicable.
            ACCEPTABLE METHODS OF DEBURRING INCLUDE:
            S120 - 15 to 54mm internal   S122 - 15 to 54mm external only    Important:
            and external.               but can re-round damaged tube.   XPress galvanised Sprinkler system tube (SC645) can
                                        Use on copper only.             only be used in sprinkler installations and should not
                                                                        be used in a general plumbing application.

                                                                       SPACING
                                                                                                  Similar consideration
                                                                        Minimum projection
                                                                                                  should be given
                                                                                                  to the distance
                                                                                                  pipe stubs project
                                                                                                  through walls or
                                                                                                  bulkheads. Refer to
                                                                                                  table on Page 137.


                                                                                                  Projection distances
                                                                        Good practice
                                                                                                  shown in the table
                                                                                                  below also ensure
                                                                                                  that the subsequent
                                                                                                  installation will be a
            TC150: 15 - 22mm external only,   Hand file.                                          convenient distance
            very good for carbon steel tube.                                                      from the wall.
            TC143 and TC147 internal only.

                    NOTE: If using plastic coated
            carbon steel system tube the plastic                                 FITTING SPACING FOR XPRESS
            coating must be removed from the
            socket depth of the fitting using the                            Sizes     Min. gap between   Min. tube projection
            S115 stripping tool from the XPress                                           fittings
            accessories range.                                               15mm         10mm          40mm
                                                                             18mm         10mm          40mm
                 Use the S115 Tube Stripper for
               removing the plastic from plastic                             22mm         10mm          40mm
                    coated carbon steel tube.                                28mm         10mm          60mm

                                                                             35mm         10mm          70mm
                                               Having deburred               42mm         20mm          70mm
                                               as above you will be          54mm         20mm          70mm
                                               left with a 1mm chamfer      66.7mm        30mm          70mm
                                          on the outside of the tube as
                                          indicated in the diagram. Wipe    76.1mm        40mm          80mm
                                          clean the tube end of remove all   88.9mm       50mm          90mm
                                          swarf and debris.                 108mm         50mm         100mm